Hospital Building - NBC Table 7

Hospital Building - Less than 15m in height with plot area up to 1000mUp to ground plus one storey, with bedsGround plus two or more storey, with no bedsGround plus two or more storey, with bedsLess than 15mtr height with plot area more than 1000mtr15mtr and above but not exceeding 24mtr heightAbove 24mtr and not exceeding 45mtr height
Fire Alarm System
Manually Operated Electronic Fire Alarm Systems (MOEFA - Fire Alarm + Public Address + Talkback System)RequiredRequiredRequiredRequiredRequiredRequired
Automatic Fire Detection and Alarm SystemNot RequiredRequiredRequiredRequiredRequiredRequired
Fire Fighting System
Fire ExtinguisherRequiredRequiredRequiredRequiredRequiredRequired
First Aid Hose ReelRequiredRequiredRequiredRequiredRequiredRequired
Wet RiserNot RequiredNot RequiredRequiredRequiredRequiredRequired
Down ComerNot RequiredRequiredNot RequiredNot RequiredNot RequiredNot Required
Yard HydrantNot RequiredNot RequiredNot RequiredRequiredRequiredRequired
Automatic Sprinkler SystemRequiredRequiredRequiredRequiredRequiredRequired
Water Supply (ltr) for Under-ground Static Water Storage Tank Combined Capacity for Wet Riser, Yard Hydrant and Sprinkers per set of PumpsNot RequiredNot Required75000100000150000200000
Pump Capacity for Pump Near Underground Static Water Storage Tank (Fire Pump) with Minimum Pressure of 3.5 kg/cm2 at Remotest LocationNot RequiredNot RequiredNot Required(see Note 14)(see Note 10)(see Note 11)
Water Supply (ltr) for Terrace Tank over Respective Tower Terrace5000 (5000) (see Note 6)10000 (5000) (see Note 6)10000100002000020000
Pump Capacity at the terrace tank level with minimum pressure of 3.5 kg/cm2450 (450) (see Note 6)900 (450) (see Note 6)Not RequiredNot RequiredNot RequiredNot Required