Institutional Building - NBC Table 7

Institutional building-Less than 15m in height with plot area up to 1000mUp to ground plus one storey, with bedsGround plus two or more storey, with no bedsGround plus two or more storey, with bedsLess than 15mtr height with plot area more than 1000mtr15mtr and above but not exceeding 24mtr heightAbove 24mtr and not exceeding 45mtr heightb) Custodial and Penal and Metal-less than 10m in height - Up to 300 persons.More than 300 persons10mtr and above but not exceeding 15mtr height15mtr and above but not exceeding 24mtr height24mtr and above but not exceeding 30mtr height
Fire Alarm System
Manually Operated Electronic Fire Alarm Systems (MOEFA - Fire Alarm + Public Address + Talkback System)RequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequired
Automatic Fire Detection and Alarm SystemNot RequiredRequiredRequiredRequiredRequiredRequiredNot RequiredNot RequiredRequiredRequiredRequired
Fire Fighting System
Fire ExtinguisherRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequired
First Aid Hose ReelRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequired
Wet RiserNot RequiredNot RequiredRequiredRequiredRequiredRequiredNot RequiredNot RequiredRequiredRequiredRequired
Down ComerNot RequiredRequiredNot RequiredNot RequiredNot RequiredNot RequiredNot RequiredRequiredNot RequiredNot RequiredNot Required
Yard HydrantNot RequiredNot RequiredNot RequiredRequiredRequiredRequiredNot RequiredNot RequiredRequiredRequiredRequired
Automatic Sprinkler SystemRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequired see note 4RequiredRequired
Water Supply (ltr) for Under-ground Static Water Storage Tank Combined Capacity for Wet Riser, Yard Hydrant and Sprinkers per set of PumpsNot RequiredNot Required75000100000150000200000RequiredRequired1000015000020000
Pump Capacity for Pump Near Underground Static Water Storage Tank (Fire Pump) with Minimum Pressure of 3.5 kg/cm2 at Remotest LocationNot RequiredNot RequiredNot Required(see Note 14)(see Note 10)(see Note 11)RequiredRequiredsee note 10see note 11see note11
Water Supply (ltr) for Terrace Tank over Respective Tower Terrace5000 (5000) (see Note 6)10000 (5000) (see Note 6)1000010000200002000010000 (5000) (see Note 6)15000 (5000) (see Note 6)5000 (5000) (see Note 6)1000020000
Pump Capacity at the terrace tank level with minimum pressure of 3.5 kg/cm2450 (450) (see Note 6)900 (450) (see Note 6)Not RequiredNot RequiredNot RequiredNot Required450 (450) (see Note 6)950 (450) (see Note 6)Not RequiredNot RequiredNot Required