| Fire Alarm System | | | | | | |
| Manually Operated Electronic Fire Alarm Systems (MOEFA - Fire Alarm + Public Address + Talkback System) | Not Required | | Required | Required | Required | Required |
| Automatic Fire Detection and Alarm System | Not Required | | Required | Required | Required | Not Required |
| Fire Fighting System | | | | | | |
| Fire Extinguisher | Required | | Required | Required | Required | Required |
| First Aid Hose Reel | Required | | Required | Required | Required | Required |
| Wet Riser | Not Required | | Required | Required | Required | Required |
| Down Comer | Not Required | | Not Required | Not Required | Not Required | Not Required |
| Yard Hydrant | Not Required | | Required | Required | Required | Required |
| Automatic Sprinkler System | Required | | Required | Required | Required | Required |
| Water Supply (ltr) for Under-ground Static Water Storage Tank Combined Capacity for Wet Riser, Yard Hydrant and Sprinkers per set of Pumps | Not Required | | 50000 | 75000 | 100000 | 150000 |
| Pump Capacity for Pump Near Underground Static Water Storage Tank (Fire Pump) with Minimum Pressure of 3.5 kg/cm2 at Remotest Location | Not Required | | see note 14 | see note 10 | see note 10 | see note 11 |
| Water Supply (ltr) for Terrace Tank over Respective Tower Terrace | 25000 | | 10000 | 10000 | 10000 | 10000 |
| Pump Capacity at the terrace tank level with minimum pressure of 3.5 kg/cm2 | 900 | | 450 | 450 | 450 | 900 |