Fire Alarm System | | | | | | |
Manually Operated Electronic Fire Alarm Systems (MOEFA - Fire Alarm + Public Address + Talkback System) | Not Required | | Required | Required | Required | Required |
Automatic Fire Detection and Alarm System | Not Required | | Required | Required | Required | Not Required |
Fire Fighting System | | | | | | |
Fire Extinguisher | Required | | Required | Required | Required | Required |
First Aid Hose Reel | Required | | Required | Required | Required | Required |
Wet Riser | Not Required | | Required | Required | Required | Required |
Down Comer | Not Required | | Not Required | Not Required | Not Required | Not Required |
Yard Hydrant | Not Required | | Required | Required | Required | Required |
Automatic Sprinkler System | Required | | Required | Required | Required | Required |
Water Supply (ltr) for Under-ground Static Water Storage Tank Combined Capacity for Wet Riser, Yard Hydrant and Sprinkers per set of Pumps | Not Required | | 50000 | 75000 | 100000 | 150000 |
Pump Capacity for Pump Near Underground Static Water Storage Tank (Fire Pump) with Minimum Pressure of 3.5 kg/cm2 at Remotest Location | Not Required | | see note 14 | see note 10 | see note 10 | see note 11 |
Water Supply (ltr) for Terrace Tank over Respective Tower Terrace | 25000 | | 10000 | 10000 | 10000 | 10000 |
Pump Capacity at the terrace tank level with minimum pressure of 3.5 kg/cm2 | 900 | | 450 | 450 | 450 | 900 |