NXPCFS112 - Addressable Smoke Detector
Automatic Fire Detection Using Addressable Smoke Sensor
Smoke Detector Placement and Spacing Guidelines
Sloped Ceilings with Beam Pockets
-Beam Pocket Locations: Spot-type detectors should be located at the bottom of beams.
-Ceiling Height: Measure ceiling height as the average height across the slope.
-Spacing:
– For beam depths ≤ 10% of ceiling height, detectors should be spaced no more than three beams apart, not exceeding smooth ceiling spacing.
– For beam depths > 10% of ceiling height, detectors should be spaced no more than two beams apart, with spacing not closer than 40% of ceiling height, and not exceeding 50% of smooth ceiling spacing.
Sloped Ceilings with Solid Joists
–Detector Placement: Detectors should be installed on the bottom of the joists.
Peaked Ceilings
–Initial Placement: Detectors should be placed within 36 inches (910 mm) of the peak, measured horizontally.
–Additional Detectors: Additional detectors, if needed, should be spaced based on the horizontal projection of the ceiling.
Shed Ceilings
–Initial Placement: Detectors should be placed within 1 mtr of the high side of the ceiling, measured horizontally.
–Additional Detectors: Additional detectors, if necessary, should be spaced according to the horizontal projection of the ceiling.
Raised Floors and Suspended Ceilings
–Separate Spaces: Areas beneath raised floors and above suspended ceilings should be treated as separate rooms for smoke detector spacing.
–Detector Requirements: Detectors beneath raised floors or above suspended ceilings cannot replace detectors within the main room.
–Raised Floors: Detectors installed beneath raised floors should comply with general smoke detector spacing guidelines.
–Suspended Ceilings: Detectors installed above suspended ceilings should follow the spacing requirements for the specific ceiling configuration.
INSPECTION, TESTING, AND MAINTENANCE
General
A well-designed and properly installed automatic fire alarm system requires continuous high standards of maintenance and supervision to ensure reliable, trouble-free operation. Regular inspections and scheduled preventive maintenance are essential, covering all system components.
Initial Installation Inspection & Tests
– A visual inspection should be conducted to verify proper placement of all detectors, ensuring they are correctly mounted and connected.
– Smoke detectors should be tested with smoke or an approved aerosol to ensure they initiate an alarm when smoke enters the chamber.
– To ensure smoke detectors are within their sensitivity range, use a calibrated test method, a manufacturer’s approved instrument, or other approved testing equipment.
– Detectors found to have sensitivity outside the approved range should be replaced.
Servicing & Periodic Maintenance
– For reliable servicing, establish a maintenance contract with a qualified contractor or ensure at least one trained employee is responsible for basic servicing, including routine sensitivity checks.
– For institutions like hospitals or hotels, ensure an engineer is available for emergency service, with a 24-hour response time. Protective measures should be taken if the premises are unoccupied.
Maintenance Schedule
– Users must obtain specific instructions from manufacturers or installers regarding routine maintenance and testing procedures.
– Maintenance routines should reflect environmental conditions; for example, detectors in harsh conditions need more frequent checks. Notify occupants if tests will activate alarms.
Annual Inspection Tests
– Annual tests should include the routine checks of detectors. At least 20% of detectors should be tested annually, ensuring that all detectors are tested over a 5-year period.
– Inspect cables and equipment for security and damage.
– Perform electrical tests every three years and document any defects.
– Record any defects found and remedied in the logbook.
General Points About Detectors
Ensure that detectors’ sensitivity ranges meet the specified requirements. Regular sensitivity checks should be carried out to maintain correct sensitivity levels throughout the service life of the installation.
Cleaning and Maintenance
Detectors should be cleaned every 3 months or more often, depending on environmental conditions. Follow manufacturer instructions for cleaning, checking, and adjusting sensitivity.
Tests Following an Alarm or Fire
Test all detectors exposed to fire conditions according to the annual inspection procedures. Inspect battery chargers and check for system-wide damage.
System Disconnection During Testing
To minimize disruption, avoid alarm activation during testing. Replace any detectors removed for servicing to ensure system contin.
What are the Vulnerabilites of false Fire Alarms due to smoke detectors Automatic fire detection primarily relies on smoke detectors
Failure or Delay in Smoke Detection:
Over time, smoke detectors can lose sensitivity, typically within two to three years, though cheaper models may lose sensitivity in under one year. This degradation impairs their ability to detect smoke effectively, leading to delayed or missed alarms and undermining the purpose of their installation.
Solution:
National and international codes and standards mandate periodic calibration of smoke detectors. To ensure reliable performance:
Select a reputable OEM that guarantees calibration services for at least five years.
Ensure availability of spare parts and service support for at least five years.
Managing False Alarms:
Contamination of Smoke Detectors:
Contamination can cause false alarms. Modern control panels and smoke detectors can indicate contamination levels and alert users, helping identify and clean affected detectors to maintain optimal performance. Some control panels can differentiate between dust and smoke, which helps reduce false alarm rates.
Preliminary Stage Alarm to Avoid False Alarms:
Since 95% of smoke incidents are not due to fire, advanced fire alarm panels and smoke detectors provide an initial alert to the control panel. This preliminary alarm allows a 30 to 45-second analysis period to determine if the smoke is from a fire. If not, the system will reset automatically to prevent false alarms, while giving emergency monitoring staff time to verify the situation. If the monitoring staff and fire alarm panel cannot confirm a fire, an external alarm will be triggered.