Assembly Building - NBC Table 7

Assembly building-Less than 10m in heightUp to 300 personsMore tham 300 personsAbove 10mtr but not exceeding 15mtr heightAbove 15mtr but not exceeding 24mtr heightAbove 24mtr but not exceeding 30mtr height
Fire Alarm System
Manually Operated Electronic Fire Alarm Systems (MOEFA - Fire Alarm + Public Address + Talkback System)RequiredRequiredRequired (see note 1)RequiredRequired
Automatic Fire Detection and Alarm SystemNot RequiredNot RequiredRequiredRequiredRequired
Fire Fighting System
Fire ExtinguisherRequiredRequiredRequiredRequiredRequired
First Aid Hose ReelRequiredRequiredRequiredRequiredRequired
Wet RiserNot RequiredNot RequiredRequiredRequiredRequired
Down ComerRequiredRequiredNot RequiredNot RequiredNot Required
Yard HydrantNot RequiredNot RequiredNot RequiredRequiredRequired
Automatic Sprinkler SystemRequired(see note 1)Required(see note 1)Required(see note 1)RequiredRequired
Water Supply (ltr) for Under-ground Static Water Storage Tank Combined Capacity for Wet Riser, Yard Hydrant and Sprinkers per set of PumpsNot RequiredNot Required100000150000200000
Pump Capacity for Pump Near Underground Static Water Storage Tank (Fire Pump) with Minimum Pressure of 3.5 kg/cm2 at Remotest LocationNot RequiredNot RequiredSee note 10See note 10See note 11
Water Supply (ltr) for Terrace Tank over Respective Tower Terrace20000 (5000) (see Note 6)25000 (5000) (see Note 6)5000 (5000) (see Note 6)1000020000
Pump Capacity at the terrace tank level with minimum pressure of 3.5 kg/cm2450 (450) (see Note 6)900 (450) (see Note 6)450 (450) (see Note 6)Not RequiredNot Required