Business Building - NBC Table 7

Business building-Less than 10m in heightLess than 10mtr heightAbove 10mtr but not exceeding 15mtr heightAbove 15mtr and up to 24mtr heightAbove 24mtr and up to 30mtr heightAbove 30mtr height
Fire Alarm System
Manually Operated Electronic Fire Alarm Systems (MOEFA - Fire Alarm + Public Address + Talkback System)RequiredRequiredRequiredRequiredRequired
Automatic Fire Detection and Alarm SystemNot RequiredRequiredRequiredRequiredRequired
Fire Fighting System
Fire ExtinguisherRequiredRequiredRequiredRequiredRequired
First Aid Hose ReelRequiredRequiredRequiredRequiredRequired
Wet RiserNot RequiredRequiredRequiredRequiredRequired
Down ComerRequiredNot RequiredNot RequiredNot RequiredNot Required
Yard HydrantNot RequiredNot RequiredRequiredRequiredRequired
Automatic Sprinkler SystemRequired see note 4Required see note 4RequiredRequiredRequired
Water Supply (ltr) for Under-ground Static Water Storage Tank Combined Capacity for Wet Riser, Yard Hydrant and Sprinkers per set of PumpsNot Required50000100000150000200000
Pump Capacity for Pump Near Underground Static Water Storage Tank (Fire Pump) with Minimum Pressure of 3.5 kg/cm2 at Remotest LocationNot RequiredSee note 14See note 10See note 11See note 12
Water Supply (ltr) for Terrace Tank over Respective Tower Terrace10000 (5000) (see Note 6)5000 (5000) (see Note 6)100002000020000
Pump Capacity at the terrace tank level with minimum pressure of 3.5 kg/cm2450 (450) (see Note 6)450 (450) (see Note 6)Not RequiredNot RequiredNot Required