Educational Building - NBC Table 7

Educational building-Less than 15m in heightGround plus one or more storeys15mtr above but not exceeding 24mtr heightAbove 24mtr but not exceeding 30mtr height
Fire Alarm System
Manually Operated Electronic Fire Alarm Systems (MOEFA - Fire Alarm + Public Address + Talkback System)Not RequiredRequiredRequired
Automatic Fire Detection and Alarm SystemNot RequiredNot RequiredNot Required
Fire Fighting System
Fire ExtinguisherRequiredRequiredRequired
First Aid Hose ReelRequiredRequiredRequired
Wet RiserNot RequiredNot RequiredRequired
Down ComerNot RequiredRequiredNot Required
Yard HydrantNot RequiredNot RequiredRequired
Automatic Sprinkler SystemRequiredRequiredRequired
Water Supply (ltr) for Under-ground Static Water Storage Tank Combined Capacity for Wet Riser, Yard Hydrant and Sprinkers per set of PumpsNot RequiredNot Required50000
Pump Capacity for Pump Near Underground Static Water Storage Tank (Fire Pump) with Minimum Pressure of 3.5 kg/cm2 at Remotest LocationNot RequiredNot Requiredsee note 14
Water Supply (ltr) for Terrace Tank over Respective Tower Terrace10000 (5000) (see Note 6)25000(5000) (see Note 6)
Pump Capacity at the terrace tank level with minimum pressure of 3.5 kg/cm2450 (450) (see Note 6)900Not Required