Hazard Building - NBC Table 7

Hazardous building-Up to 15mtr in heightSingle storey buildingMore than one floor building but not exceeding 15mtr
Fire Alarm System
Manually Operated Electronic Fire Alarm Systems (MOEFA - Fire Alarm + Public Address + Talkback System)RequiredRequired
Automatic Fire Detection and Alarm SystemRequiredRequired
Fire Fighting System
Fire ExtinguisherRequiredRequired
First Aid Hose ReelRequiredRequired
Wet RiserRequiredRequired
Down ComerNot RequiredRequired
Yard HydrantRequiredRequired
Automatic Sprinkler SystemRequiredRequired
Water Supply (ltr) for Under-ground Static Water Storage Tank Combined Capacity for Wet Riser, Yard Hydrant and Sprinkers per set of PumpsMinimum 240min fire fighting requirementsMinimum 240min fire fighting requirements
Pump Capacity for Pump Near Underground Static Water Storage Tank (Fire Pump) with Minimum Pressure of 3.5 kg/cm2 at Remotest LocationSee note 21See note 21
Water Supply (ltr) for Terrace Tank over Respective Tower TerraceNot Required50000
Pump Capacity at the terrace tank level with minimum pressure of 3.5 kg/cm2Not Required900