Hotel Building - NBC Table 7

Hotels-Less than 15m in heightFloor area not exceeding 300m on any of the floorFloor area exceeding 300m but not more 1000m on any of the floorFloor area exceeding 1000m on any of the floor15mtr and above but not exceeding 30mtrAbove 30mtr in heightHotel (A-6)
Fire Alarm System
Manually Operated Electronic Fire Alarm Systems (MOEFA - Fire Alarm + Public Address + Talkback System)RequiredRequiredRequiredRequiredRequiredRequired
Automatic Fire Detection and Alarm SystemNot RequiredRequiredRequiredRequiredRequiredRequired
Fire Fighting System
Fire ExtinguisherRequiredRequiredRequiredRequiredRequiredRequired
First Aid Hose ReelRequiredRequiredRequiredRequiredRequiredRequired
Wet RiserNot RequiredRequiredRequiredRequiredRequiredRequired
Down ComerNot RequiredNot RequiredNot RequiredNot RequiredNot RequiredNot Required
Yard HydrantNot RequiredNot RequiredRequiredRequiredRequiredRequired
Automatic Sprinkler SystemRequired (see not 4)Required (see not 4)RequiredRequiredRequiredRequired
Water Supply (ltr) for Under-ground Static Water Storage Tank Combined Capacity for Wet Riser, Yard Hydrant and Sprinkers per set of PumpsNot Required10000 for every 500m floor area subject to minimum of 50000(see note 7)100000 see note 15150000200000250000
Pump Capacity for Pump Near Underground Static Water Storage Tank (Fire Pump) with Minimum Pressure of 3.5 kg/cm2 at Remotest LocationNot Requiredsee note 14 in case of provision of wet risersee note 14 & 15see note 11see note 11see note 12
Water Supply (ltr) for Terrace Tank over Respective Tower Terrace5000 (5000) (see Note 6)10000 (5000) (see Note 6)10000 see note 4200002000020000
Pump Capacity at the terrace tank level with minimum pressure of 3.5 kg/cm2450 (450) (see Note 6)450 (450) (see Note 6)Not RequiredRequiredRequiredNot Required