Fire Alarm System | | | | | | | | | | | | | | | | | |
Manually Operated Electronic Fire Alarm Systems (MOEFA - Fire Alarm + Public Address + Talkback System) | | Not Required | Not Required | Required | Required | | Not Required | Not Required | Required | Required | Required | | Not Required | Required | Required | Required | Required |
Automatic Fire Detection and Alarm System | | Not Required | Not Required | Not Required | Required | | Not Required | Not Required | Required | Required | Required | | Not Required | Required | Required | Required | Required |
Fire Fighting System | | | | | | | | | | | | | | | | | |
Fire Extinguisher | | Required | Required | Required | Required | | Required | Required | Required | Required | Required | | Required | Required | Required | Required | Required |
First Aid Hose Reel | | Not Required | Required | Required | Required | | Required | Required | Required | Required | Required | | Required | Required | Required | Required | Required |
Wet Riser | | Not Required | Not Required | Not Required | Required | | Not Required | Not Required | Not Required | Required | Required | | Not Required | Not Required | Required | Required | Required |
Down Comer | | Not Required | Required-see note 8 | Required | Not Required | | Not Required | Not Required | Required | Not Required | Not Required | | Not Required | Not Required | Not Required | Not Required | Not Required |
Yard Hydrant | | Not Required | Not Required | Not Required | Required | | Not Required | Not Required | Not Required | Required | Required | | Not Required | Not Required | Not Required | Required | Required |
Automatic Sprinkler System | | Required-see note 4 | Required-see note 4 | Required-see note 4 | Required-see note 4 | | Required | Required | Required | Required | Required | | Required | Required | Required | Required | Required |
Water Supply (ltr) for Under-ground Static Water Storage Tank Combined Capacity for Wet Riser, Yard Hydrant and Sprinkers per set of Pumps | | Not Required | Not Required | Not Required | 75000 | | Not Required | Not Required | Not Required | 100000 | 150000 | | Not Required | Not Required | 50000 | 100000 | 150000 |
Pump Capacity for Pump Near Underground Static Water Storage Tank (Fire Pump) with Minimum Pressure of 3.5 kg/cm2 at Remotest Location | | Not Required | Not Required | Not Required | see note 14 | | Not Required | Not Required | Not Required | see note 14 | see note 11 | | Not Required | Not Required | see note 14 | see note 10 | see note 11 |
Water Supply (ltr) for Terrace Tank over Respective Tower Terrace | | 5000 (see Note 5) | 20000 (5000 see Note 6) | 20000 (5000 see Note 6) | 5000 (see Note 6) | | 10000 | 20000 | 50000 | 10000 | 20000 | | 10000 | 25000 | 10000 | 20000 | 20000 |
Pump Capacity at the terrace tank level with minimum pressure of 3.5 kg/cm2 | | 450 (see Note 5) | 450 (450) (see Note 6) | 450 (450) (see Note 6) | Not Required | | 450 | 900 | 900 | Not Required | Not Required | | 900 | 900 | Not Required | Not Required | Not Required |