Industrial Building - NBC Table 7

Industrial Buildings-A)Low hazard (see note 18)Covered area up to 100mCovered area more than 100mtr up to 500mCovered area more than 500mtr (for building height up to 15mtr)Covered area more than 500mtr (for building height above 15mtr)B) Moderate Hazard (G-2)(see note 18)Covered area up to 100mCovered area more than 100mtr up to 500mCovered area more than 500mtr up to 1000 for height up to 15mCovered area more than 500mtr up to 1000 for height above 15mCovered area more than 1000mc) High Hazard (g-3 see note 19)Coverd area up to 50mCovered area more than 50mtr and up to 150mtrCovered area more than 150mtr and up to 300mtrCovered area more than 300mtr and up to 500mtrCovered area more than 500mtr
Fire Alarm System
Manually Operated Electronic Fire Alarm Systems (MOEFA - Fire Alarm + Public Address + Talkback System)Not RequiredNot RequiredRequiredRequiredNot RequiredNot RequiredRequiredRequiredRequiredNot RequiredRequiredRequiredRequiredRequired
Automatic Fire Detection and Alarm SystemNot RequiredNot RequiredNot RequiredRequiredNot RequiredNot RequiredRequiredRequiredRequiredNot RequiredRequiredRequiredRequiredRequired
Fire Fighting System
Fire ExtinguisherRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequired
First Aid Hose ReelNot RequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequired
Wet RiserNot RequiredNot RequiredNot RequiredRequiredNot RequiredNot RequiredNot RequiredRequiredRequiredNot RequiredNot RequiredRequiredRequiredRequired
Down ComerNot RequiredRequired-see note 8RequiredNot RequiredNot RequiredNot RequiredRequiredNot RequiredNot RequiredNot RequiredNot RequiredNot RequiredNot RequiredNot Required
Yard HydrantNot RequiredNot RequiredNot RequiredRequiredNot RequiredNot RequiredNot RequiredRequiredRequiredNot RequiredNot RequiredNot RequiredRequiredRequired
Automatic Sprinkler SystemRequired-see note 4Required-see note 4Required-see note 4Required-see note 4RequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequiredRequired
Water Supply (ltr) for Under-ground Static Water Storage Tank Combined Capacity for Wet Riser, Yard Hydrant and Sprinkers per set of PumpsNot RequiredNot RequiredNot Required75000Not RequiredNot RequiredNot Required100000150000Not RequiredNot Required50000100000150000
Pump Capacity for Pump Near Underground Static Water Storage Tank (Fire Pump) with Minimum Pressure of 3.5 kg/cm2 at Remotest LocationNot RequiredNot RequiredNot Requiredsee note 14Not RequiredNot RequiredNot Requiredsee note 14see note 11Not RequiredNot Requiredsee note 14see note 10see note 11
Water Supply (ltr) for Terrace Tank over Respective Tower Terrace5000 (see Note 5)20000 (5000 see Note 6)20000 (5000 see Note 6)5000 (see Note 6)10000200005000010000200001000025000100002000020000
Pump Capacity at the terrace tank level with minimum pressure of 3.5 kg/cm2450 (see Note 5)450 (450) (see Note 6)450 (450) (see Note 6)Not Required450900900Not RequiredNot Required900900Not RequiredNot RequiredNot Required