NXSFS01 - Standard for Addressable Manually Operated Fire Alarm System (MOEFA)

According to the National Building Code (NBC) 2016, a Manually Operated Fire Alarm System is defined as comprising the following components:
1. Manual Call Point Fire Signaling System
2. Public Address (PA) System
3. Talkback Speaker System

The NBC also outlines requirements for the integration of electromechanical systems, voice alarm systems, and other related elements.

Traditional or conventional engineering techniques for MOEFA and automatic fire detection systems often face challenges in ensuring full compliance with NBC standards. Therefore, Connexxity’s guidelines are based on Addressable Systems to address these challenges effectively.

Standards for Achieving MOEFA Compliance:

1. NXSFS04 – Standard for Addressable Manual Call Point Fire Signaling System
2. NXSFS05 – Standard for Addressable Public Address System
3. NXSFS06 – Standard for Addressable Talkback System

For small-scale applications, these three systems can share a single cable and control panel.

For medium and large-scale applications, the Talkback System should be autonomous to ensure optimal performance.

If the Talkback speaker is used for both PA and Talkback applications, the following volume limits must be adhered to:
Talkback Mode: Maximum volume of 65 dB
PA Mode: Maximum volume of 90 dB

Once the PA or Talkback system is commissioned, no further modifications or adjustments should be allowed by FCC operators to ensure system integrity and compliance.

NBC 2016 Requirements:

– Voice alarms must be used instead of hooters or sirens, in English, Hindi, or local languages.
– Alarms should include flashing lights.
– Access controlled doors and emergency lighting must deactivate automatically during alarms.

Important Considerations:

– All fire warning system cables and instruments must have fault monitoring systems.
– Cables must be mechanically and fire-resistant to ensure functionality during fires.

Additional Recommendations:

– Regularly monitor the health of fire detection and warning equipment, including speakers and talkback systems.
– Avoid using systems that do not meet these standards, such as lifestyle commercial speaker systems or those lacking fault monitoring.

Items Used For MOEFA:

  • Standard for Manual Call Point – (NXPCFS101)
  • Standard for Talkback Speaker – (NXPCFS104)
  • Standard for PA Speaker – ( NXPCFS102)
  • Standard for Short Circuit Isolator – (NXPCFS111)
  • Standard for Monitor Module – (NXPCFS110)
  • Standard for Control Module – (NXPCFS108)

Forms and Checklist

 

1NXF-101FZone Details
2NXF-102FVoice Message
3NXF-103FPublic Address System
4NXF-105FControl Module
5NXF-106FIsolator
6NXF-107FManual Call Point
7NXF-108FMonitor Module
8NXF-110FTalkback
9NXF-111FStrobe
10NXF-112FIsolator Current
11NXF-113FBill of Materials
12NXF-114FControl Panel
13NXF-115FCable Schedule