Storage Building - NBC Table 7

Storage buildingBelow 15mtr height and coverded area less than 250mtrBelow 15mtr height and coverded area more than 250mtr1)Ground floor only2)Ground plus one floor only2)More than Ground plus one floorMulti-Level car parking
Fire Alarm System
Manually Operated Electronic Fire Alarm Systems (MOEFA - Fire Alarm + Public Address + Talkback System)Not RequiredRequiredRequiredRequiredRequired
Automatic Fire Detection and Alarm SystemNot RequiredRequiredRequiredRequiredNot Required
Fire Fighting System
Fire ExtinguisherRequiredRequiredRequiredRequiredRequired
First Aid Hose ReelRequiredRequiredRequiredRequiredRequired
Wet RiserNot RequiredRequiredRequiredRequiredRequired
Down ComerNot RequiredNot RequiredNot RequiredNot RequiredNot Required
Yard HydrantNot RequiredRequiredRequiredRequiredRequired
Automatic Sprinkler SystemRequiredRequiredRequiredRequiredRequired
Water Supply (ltr) for Under-ground Static Water Storage Tank Combined Capacity for Wet Riser, Yard Hydrant and Sprinkers per set of PumpsNot Required5000075000100000150000
Pump Capacity for Pump Near Underground Static Water Storage Tank (Fire Pump) with Minimum Pressure of 3.5 kg/cm2 at Remotest LocationNot Requiredsee note 14see note 10see note 10see note 11
Water Supply (ltr) for Terrace Tank over Respective Tower Terrace2500010000100001000010000
Pump Capacity at the terrace tank level with minimum pressure of 3.5 kg/cm2900450450450900